Rafiki problem

$
0
0
Public house with 11 "lodges" in the ground,  Plastic 4 Zone Rafiki controls interconnected into an 8 Zone metal Rafiki controls


There are 11 circuits each with 1 sounder/ multi sensor & mcp

The metal controls are shafted with zones 4,5,6,7 & 8 not sounding, detecting fire or fault monitoring.

Rafiki only do upto 8 zone controls.... There is no possibility of rewiring, to put every thing onto one control panel I think my only options are

Haes 12 zone Alarmsense or Twinwire Controls with new call points, sounder bases & detectors

or

Single loop addressable running open ended,with new call points, sounder bases & detectors (I'd go kentec & apollo)

Does the forum have any other ideas ?